ZYD-I Transformer Oil Regneration Plant,vacuum dielectric oil recycling system,insulator oil purification plant
Dissolved gasses in transformer oil can cause arcing, corona discharges, and overheating--reducing the electrical efficiency and lifetime of the transformer. Likewise, water contamination at levels as low as 30 ppm (parts per million) can adversely affect the insulating strength of the oil. With ever-increasing standards for energy efficiency of power distribution transformers, the need to effectively degas will become even more important in the future. particles contamination will also affect the function of insulating oil. So we need to clean used transformer oil.
In order to achieve optimal dielectric strength and insulating performance inside of transformers and circuit breakers, dielectric oils must be kept absolutely clean and dry. Substation Maintenance Contractors and Utilities need an oil Filtration machine that can quickly and reliably process transformer oil to meet or exceed very stringent specifications, so HOPU designs and manufactures the most effective, durable, and user-friendly machine running in almost each city of China and serving customers in 40 more countries with good reputation.
Performance:
Re-refining to remove acids and particulate material
Dehydrating to remove free and dissolved water, including insulation dry-out of the windings.
Degassing to remove other dissolved combustible gases such as Acetylene, Ethylene, Ethane, Methane, Hydrogen and Carbon Monoxide, and Carbon Dioxide.
Index before purification(from customer for your reference):
water content≤50ppm
gas content≤10 %(by volume)
breakdown voltage≥30KV/2.5mm
particle qty≤70000 (5-50micron)
Index after purification (test at oil-outlet of the machine):
water content≤5ppm
gas content≤0.1%( by volume)
acetylene content:0
breakdown voltage≥75KV (Spherical polar)
particle qty in 100ml oil≤500 (5-50 micron), (0 for≥100 micron particle).
dielectric loss tgδ≤0.3% (90°C)
acid value≤0.1mgKOH/g
Technical Parameter
Parameters |
Unit |
ZYD-30 |
ZYD-50 |
ZYD-100 |
ZYD-150 |
ZYD-200 |
ZYD-250 |
ZYD-300 |
Flow |
L/h |
1800 |
3000 |
6000 |
9000 |
12000 |
15000 |
18000 |
Working vacuum |
MPa |
-0.08 ~ -0.099 |
Working Pressure |
MPa |
≤0.3 |
Breakdown Voltage |
KV |
≥65 |
Water Content |
PPM |
≤5 |
Gas Content |
% |
≤0.1 |
Impurity Size |
μ |
≤5 |
Temperature Range |
|
20 ~ 80 |
Power |
|
Three Phase 50HZ380V(as per the customer’s requirements) |
Working Noise |
dB(A) |
75 |
75 |
75 |
80 |
80 |
80 |
80 |
Heating Power |
KW |
30 |
30 |
45 |
60 |
75 |
90 |
120 |
Total Power |
KW |
35.5 |
37.5 |
52.5 |
71.4 |
86.5 |
102.5 |
135 |
Inlet/Outlet |
mm |
25 |
32 |
42 |
50 |
50 |
60 |
60 |
Weight |
Kg |
600 |
800 |
1050 |
1400 |
1800 |
2000 |
2200 |
Overall |
Length |
mm |
1050 |
1100 |
1200 |
1450 |
1600 |
1800 |
1900 |
Width |
mm |
750 |
800 |
950 |
950 |
1100 |
1200 |
1200 |
Height |
mm |
1350 |
1400 |
1500 |
1650 |
1800 |
1900 |
1900
|
Guarantee Value:
Item |
Unit |
After treatment |
Breakdown Voltage |
kV |
≥75 |
Moisture content |
PPM |
≤3 |
Gas content |
% |
≤0.1
|
Please contact for more technical details and latest price: